How to Choose a Suitable Flexible Busbar for Transformer?

1. Key Electrical Parameters

  • Material: T2 pure copper (Cu ≥99.95%), annealed soft state.
  • Current rating: Select cross‑section based on transformer rated current.
    • General design: 3–5 A/mm²
    • For transformers: use safe side: 3–3.5 A/mm² for low temperature rise.
  • Voltage level: Match insulation sleeve to transformer voltage (1kV, 10kV, 35kV).

2. Dimensions & Installation

  • Total length: Center-to-center distance of mounting holes + 10–20 mm compensation for thermal expansion and vibration.
  • End size: Match width, thickness, hole distance, hole diameter of transformer bushing or connector.
  • Flexible section: Keep at least 30–50 mm for flexibility.

3. Surface Plating

  • Indoor, dry environment: Tin-plated
  • Outdoor, coastal, corrosive: Nickel-plated
  • High current, low resistance: Silver-plated

4. Welding & Structure

  • Welding: Molecular diffusion welding (no virtual welding, low resistance, long life).
  • Insulation: Flame‑retardant heat‑shrinkable tube or silicone sleeve.
  • Structure: Two rigid ends + middle flexible layer.

Xi'an zipeng is a professional manufacturer for copper busbar, they have very richful experience in busbar customized, and they have good cooperated with worldwidely famous company, such as Schneider,GE... 