How to Choose a Suitable Flexible Busbar for Transformer ?
2026-03-04
How to Choose a Suitable Flexible Busbar for Transformer?
1. Key Electrical Parameters
- Material: T2 pure copper (Cu ≥99.95%), annealed soft state.
-
Current rating: Select cross‑section based on transformer rated current.
- General design: 3–5 A/mm²
- For transformers: use safe side: 3–3.5 A/mm² for low temperature rise.
- Voltage level: Match insulation sleeve to transformer voltage (1kV, 10kV, 35kV).
2. Dimensions & Installation
- Total length: Center-to-center distance of mounting holes + 10–20 mm compensation for thermal expansion and vibration.
- End size: Match width, thickness, hole distance, hole diameter of transformer bushing or connector.
- Flexible section: Keep at least 30–50 mm for flexibility.
3. Surface Plating
- Indoor, dry environment: Tin-plated
- Outdoor, coastal, corrosive: Nickel-plated
- High current, low resistance: Silver-plated
4. Welding & Structure
- Welding: Molecular diffusion welding (no virtual welding, low resistance, long life).
- Insulation: Flame‑retardant heat‑shrinkable tube or silicone sleeve.
- Structure: Two rigid ends + middle flexible layer.
Xi'an zipeng is a professional manufacturer for copper busbar, they have very richful experience in busbar customized, and they have good cooperated with worldwidely famous company, such as Schneider,GE...
It is a good option for all kinds of busbar supply, welcome to ask more through the mail: info@zpbusbar.com